Infrared Refrigerant Leak Sensor (NDIR) — PPM Early Warning & %LEL Safety
Winsen® infrared (NDIR) refrigerant leak sensors provide stable, selective measurement for A1, A2L, and A3 gases—R134a, R410A, R32, R454B, R1234yf/ze, R290, R600a. Choose ppm-level accuracy for early warning, or %LFL/%LEL for safety interlocks. Seamless BMS/PLC integration via 4–20 mA, RS-485 Modbus, at mga output ng relay.


Why Infrared (NDIR) for Refrigerant Leak Detection?
High Selectivity
NDIR measures gas absorption at specific IR wavelengths, delivering excellent selectivity for HFC/HFO refrigerants and robust A2L/A3 options.
Stability & Low Drift
Dual-channel optical design with reference beam minimizes temperature/ageing drift, extending calibration intervals (often 12–24 months).
Not O₂-Dependent
Infrared sensing does not require oxygen, unlike catalytic beads—ideal for machinery rooms, cold rooms, and enclosed HVAC spaces.
Model Guide — Select by Class & Measurement
Infrared (NDIR) refrigerant leak sensors and detectors for A1, A2L, and A3 gases: R32, R454B, R1234yf/ze, R134a, R410A, R290, R600a. PPM early warning & %LEL safety, 4–20 mA, RS-485 Modbus, relay outputs. OEM/ODM by Winsen® for bulk orders.
NDIR Refrigerant Sensor
Semiconductor Refrigerant Sensor
How Infrared (NDIR) Refrigerant Sensors Work
| Stage | What Happens | Benepisyo |
|---|---|---|
| Emission | IR source emits broadband light through the gas sample. | Reliable optical excitation |
| Filtering | Narrowband optical filter targets refrigerant absorption bands; a second channel serves as reference. | Gas selectivity & drift compensation |
| Detection | Photodetectors measure attenuated signal vs. reference; MCU computes concentration. | Stable ppm / %LEL output |
| Compensation | Temperature/pressure & baseline routines (e.g., ABC optional) correct drift. | Long intervals between calibrations |
Mga Karaniwang Aplikasyon
VRF/VRV indoor units & hotel rooms
Mababa ang bundok (~150–300 mm AFF) malapit sa mga panloob na unit at pooling point; i-link ang mga alarm sa fan shutdown at fresh-air purge.
Chiller & machinery rooms, compressor racks
Place near compressors, separators, valves, and low spots/sumps; use IP-rated housings and BMS interlocks.
Cold storage & refrigerated display cases
Install beneath cases and along manifolds/pipe runs; choose condensation-resistant designs and curtain/exhaust interlocks.
Mga in-row/CRAC unit ng data center
Position in return air, under raised floors, and near coils; ppm early warning protects personnel and uptime.
Heat pumps & general HVAC
For A2L/A3, use %LFL tiers (e.g., ~25% pre-alarm; ~50% main) to trigger ventilation and equipment shutdown.
Infrared vs. Other Technologies
| Teknolohiya | Pinakamahusay Para sa | Saklaw | Kalamangan | Mga pagsasaalang-alang |
|---|---|---|---|---|
| NDIR (Infrared) | A1 ppm; A2L ppm/%LEL; A3 %LEL (IR-LEL) | ppm → %LEL | High selectivity, low drift, not O₂-dependent | Higher initial cost; protect from heavy condensation/dust |
| MOS (Semiconductor) | A2L/A3%LEL | 0–100% LEL | Fast response; cost-effective | Cross-sensitivities; periodic calibration |
| Catalytic Bead | Pangkalahatang hydrocarbon (A3) | 0–100% LEL | Mature tech | Needs O₂; can be poisoned (silicones/lead) |
Placement & Setpoints — Good Practice
- Taas ng pag-mount: Most refrigerants are heavier than air ⇒ mount low; confirm with airflow studies.
- Saklaw: Approx. 5–10 m radius per sensor in open rooms; add units near valves/joints and low pockets.
- Alarm tiers: A2L/A3: pre-alarm ≈25% LFL; main ≈50% LFL. A1: ppm bands (e.g., 1,000–5,000 ppm) per spec.
- Interlocks: Pre-alarm → bentilasyon; Pangunahing → pagsasara ng kagamitan + beacon/BMS alarm.
I-finalize ang mga threshold at dami kumpara sa detalye ng iyong proyekto at mga lokal na code.
Bakit Pinipili Kami ng mga Global Client?
Ang kumpanya ay patuloy na sumusunod sa kalidad ng patakaran ng "Fine Craftsmanship, Scientific Innovation, Pursuit of Excellence, at Value-Added Service." Sa pamamagitan ng pagbabalangkas ng mga plano sa pagkontrol sa proseso ng produksyon at mga tagubilin sa trabaho, ito ay nagtatag ng isang standardized, accountable, at regulated na sistema ng pamamahala ng proseso. Bukod pa rito, ang kumpanya ay nakapag-iisa na bumuo ng isang MES production management system, na nagpapagana ng komprehensibo at visual na pamamahala sa buong workflow.

30+ TAON NG KARANASAN
R&D, manufacture and sales of sensors and sensing solutions.
KALIDAD GUARANTEE PATULOY NA PAGPAPABUTI
Kumpleto at mahigpit na kontrol sa daloy ng proseso, kasama ng mga makabuluhang pagpapabuti.


INTERNATIONAL MARKET
Maghatid ng mga sensing na produkto sa higit sa 100 bansa at rehiyon.
MATATAG NA SUPPLY CHAIN MAAASAHANG PRODUKSIYON
Mga pangunahing bahagi na hindi napapailalim sa mga hadlang, mga advanced na kagamitan para sa paggawa at pagsubok.


R&D STRENGTH TECHNOLOGY INNOVATION
200+ patents, 180+ R&D team members, self-built labs for continous innovation.
One-stop na serbisyo
Propesyonal na konsultasyon, mabilis na paghahatid, 24 na oras na suporta pagkatapos ng benta.

Leading the Industry, Innovative & Controllable Technology
With robust R&D capabilities, we maintain sustained input in R&D and unwavering commitment to technological innovation. This not only ensures that we remain at the forefront of industry but also drives continuous innovation, leading the future trend of the sensing industry.
10% R&D Input
The average annual R&D input exceeds 10% of the annual revenue.
5+ R&D Layout
With Zhengzhou headquarters as the core, a nationwide R&D and innovation system is being established, encompassing cities of Shanghai, Wuhan, Shenzhen, and Taiyuan.
180+ R&D Team
There are over 180 R&D personnel, including more than 10 with doctoral degrees and over 50 with master's degrees, who have an average of more than 8 years of experience in sensor development.
20+ Uri ng Eksperimento
Kaugnay ng gas, Kapaligiran sa Klima, EMC, Pagganap ng Elektrisidad, Pagganap ng Mekanikal, atbp.
10+ Advanced na Laboratoryo
CNAS Laboratory, MEMS Laboratory, UL Laboratory, Nanocomposite Materials Laboratory, atbp.
400+ sets Leading R&D Equipment
Cube Storage, Die Bonder, Lithography Machine, Coating Machine, SMT Placement Machine, Automatic Probe Station, atbp.
Humiling ng Konsultasyon
FAQs — Infrared (NDIR) Refrigerant Leak Sensors
Is NDIR better than MOS for refrigerants?
For ppm early warning and long-term stability, NDIR is typically preferred. For %LEL safety trips on A2L/A3 gases, NDIR-LEL or MOS can both be used depending on budget and environment.
How often do NDIR sensors need calibration?
12–24 months is common with periodic bump tests. High-dust or high-humidity sites may require more frequent checks and filter maintenance.
Where should the sensor be installed?
Near likely leak sources (compressors, valves, joints) and low-lying accumulation points; avoid strong supply air that could bypass the sensor.
Do Winsen IR sensors integrate with BMS/PLC?
Yes—native 4–20 mA, RS-485 Modbus RTU, and relay contacts make integration straightforward.
Can you customize for OEM programs?
Absolutely. We customize ranges, firmware, connectors, harnesses, housings, and branding for volume deployments.